NIBE F1345/F1355 (EB100) is connected to accumulator tanks (CP10) and charges them.
The energy is transferred via Cetetherm AquaEfficiency (EZ2) from the accumulator tanks to the tap side. The hot water is heated when needed, but not stored.
A mixing valve is built into AquaEfficiency, which reduces the risk of scalding, as well as an HWC pump which ensures that there is always hot water at the right temperature.
For maximum efficiency and optimum utilisation of the accumulator tanks, it is important to have good stratification in the tanks. The flow through the accumulator tanks is set using the trim valves (RN1-RN5). For connection according to the Tichelmann principle, only trim valve RN1.1 is required.
The controlling hot water sensor (BT6) is positioned in such a way that 1/3 of the total accumulator volume is below the sensor. The heat pump’s start and stop temperatures are affected by the location of the sensor as well as the charge power in relation to accumulator volume.
Check that "hot water, auto" is not selected in menu 5.1.11 - "pump speed heating medium".
Check that "hot water, manual" in menu 5.1.11 is set to 100%.
Start all the compressors that are connected to hot water.
Adjust the flow with the trim valve (RN1.1) so that the difference between the supply and return lines is 10 K at 55°C supply or higher (10.5 K at 45°C supply, 11 K at 35°C supply).
After each adjustment of the trim valve, allow the system to stabilise for 3 minutes before the next adjustment.
Verify the temperature difference over 10 minutes of operation.
When the correct temperature difference has been verified, select operating mode ”hot water, auto” in menu 5.1.11.
In menu 5.1.1 - "hot water settings", adjust the temperature settings for hot water charging start and stop to suitable values, depending on charge power and volume.
TIPS If you want 55°C domestic hot water, start 53°C and stop 59°C are recommended.
Set “charge method” to “target temp” in menu 5.1.1.
Once commissioning is complete, monitor one cycle to ensure that the system does not stop at high return or condenser temperature until hot water charging is complete in BT6.
Designation |
Name |
Specification |
Part No. |
Comments |
---|---|---|---|---|
-AA25-BT1 |
Outside sensor |
Included in F1345/F1355 |
||
-AA25-BT6 |
Controlling hot water sensor |
Included in F1345/F1355 |
||
-AA25-BT7 |
Display hot water sensor |
Included in F1345/F1355 |
||
-AA25-BT25 |
External supply temperature sensor |
|||
-AA25-BT63 |
External supply temperature sensor after QN10 |
|||
-AA25-BT71 |
External return line sensor |
Included in F1345/F1355 |
||
-AA25-GP10 |
External heating medium pump |
|||
-AA25-GP12.1 |
Charge pump for EB101 |
NIBE CPD 11 |
067 321 |
|
-AA25-GP12.2 |
Charge pump for EB102 |
NIBE CPD 11 |
067 321 |
|
-AA25-GP12.3 |
Charge pump for EB103 |
NIBE CPD 11 |
067 321 |
|
-AA25-GP12.4 |
Charge pump for EB104 |
NIBE CPD 11 |
067 321 |
|
-AA25-QN10 |
Reversing valve, heating/hot water |
See the valve’s manual for a port description. |
||
-EB100 |
Heat pump system |
F1345/F1355 |
||
-EP14 |
Cooling module |
See the Installer Manual for more information about the relevant cooling module. |
||
-EP15 |
Cooling module |
See the Installer Manual for more information about the relevant cooling module. |
||
-BT6 |
Controlling hot water sensor |
Included in F1345/F1355 |
||
-EB100-BT6 |
Controlling hot water sensor |
Included in F1345/F1355 |
||
-EB100-BT7 |
Display hot water sensor |
Included in F1345/F1355 |
||
-BT7 |
Display hot water sensor |
Included in F1345/F1355 |
||
-EB100-BT25 |
External supply temperature sensor |
Included in F1345/F1355 |
||
-EB100-BT71 |
External return line sensor |
Included in F1345/F1355 |
||
-EB100-GP7 |
External brine pump |
|||
-EB100-GP10 |
External heating medium pump |
|||
-EB100-QN10 |
Reversing valve, heating/hot water |
See the valve’s manual for a port description. |
||
-BT1 |
Outside sensor |
Included in F1345/F1355 |
||
-BT25 |
External supply temperature sensor |
|||
-EP4 |
Heat exchanger, groundwater |
|||
-FL10 |
Safety valve, brine |
|||
-FL11 |
Safety valve, brine |
|||
-FL12 |
Safety valve, heating medium |
|||
-FL13 |
Safety valve, heating medium |
|||
-GP16 |
Circulation pump, brine |
Included in F1355 40/60 |
||
-QN11 |
Shuttle valve |
|||
-QM12 |
Filling valve, brine |
|||
-QM21 |
Vent valve, brine |
|||
-QM31 |
Shut-off valve, heating medium supply line |
|||
-QM32 |
Shut-off valve, heating medium return line |
|||
-QM33 |
Shut-off valve, brine in |
|||
-QM40 |
Shut-off valve |
|||
-QM42 |
Shut-off valve, brine in |
|||
-QM50 |
Shut off valve, brine |
|||
-QM51 |
Shut off valve, brine |
|||
-QM52 |
Shut off valve, brine |
|||
-QM53 |
Shut off valve, brine |
|||
-QM54 |
Shut-off valve, heating medium |
|||
-QM55 |
Shut-off valve, heating medium |
|||
-QM56 |
Shut-off valve, heating medium |
|||
-QM57 |
Shut-off valve, heating medium |
|||
-QZ2 |
Filterball, heating medium |
Included in F1345 |
F1355 includes a particle filter, which should be supplemented with a shut-off valve. |
|
-QZ4 |
Filterball, heating medium |
Included in F1345 |
F1355 includes a particle filter, which should be supplemented with a shut-off valve. |
|
-QZ5 |
Filterball, heating medium |
Included in F1345 |
F1355 includes a particle filter, which should be supplemented with a shut-off valve. |
|
-RM10 |
Non-return valve |
Included in F1345/F1355 |
||
-RM11 |
Non-return valve |
Included in F1345/F1355 |
||
-RM12 |
Non-return valve |
Included in F1345/F1355 |
||
-RM13 |
Non-return valve |
Included in F1345/F1355 |
||
-RN20 |
Trim valve |
|||
-RN21 |
Trim valve |
|||
-EB101-FL10 |
Safety valve, heating medium |
|||
-EB101-QM1 |
Drain valve, heating medium |
|||
-EB101-QM40 |
Shut-off valve, heating medium |
|||
-EB101-QZ2 |
Filterball, heating medium |
Included in F1345 |
||
-EB101-RM1 |
Non-return valve, heating medium |
|||
-EB102 |
Heat pump system (Slave 2) |
|||
-EB102-FL10 |
Safety valve, heating medium |
|||
-EB102-QM1 |
Drain valve, heating medium |
|||
-EB102-QM40 |
Shut-off valve, heating medium |
|||
-EB102-QZ2 |
Filterball, heating medium |
Included in F1345 |
||
-EB102-RM1 |
Non-return valve, heating medium |
|||
-EB103 |
Heat pump system (Slave 3) |
|||
-EB103-AA25 |
AXC module |
Included in AXC 50 |
067 060 |
|
-EB103-FL10 |
Safety valve, heating medium |
|||
-EB103-QM1 |
Drain valve, heating medium |
|||
-EB103-QM40 |
Shut-off valve, heating medium |
|||
-EB103-QZ2 |
Filterball, heating medium |
Included in F1345 |
||
-EB103-RM1 |
Non-return valve, heating medium |
|||
-EB104 |
Heat pump system (Slave 4) |
|||
-EB104-FL10 |
Safety valve, heating medium |
|||
-EB104-QM1 |
Drain valve, heating medium |
|||
-EB104-QM40 |
Shut-off valve, heating medium |
|||
-EB104-QZ2 |
Filterball, heating medium |
Included in F1345 |
||
-EB104-RM1 |
Non-return valve, heating medium |
|||
XL |
XL connections |
|||
1 |
Heating medium connection, supply |
|||
XL1 |
Heating medium connection, supply |
|||
2 |
Heating medium connection, return |
|||
XL2 |
Heating medium connection, return |
|||
3 |
Cold water connection |
|||
4 |
Hot water connection |
|||
5 |
Hot water circulation connection |
|||
6 |
Brine connection, supply |
|||
7 |
Brine connection, return |
|||
8 |
Docking connection, supply |
|||
9 |
Docking connection, return |
|||
13 |
Solar heat connection, supply |
|||
14 |
Solar heat connection, return |
|||
18 |
Docking connection, supply |
|||
19 |
Docking connection, return |
|||
29 |
T&Pvalve |
|||
30 |
Expansion vessel connection |
|||
39 |
Docking connection, pool |
|||
0 |
Exhaust air recovery 1 |
|||
-AZ10 |
Exhaust air module |
NIBE FLM |
067 627 |
|
-AZ10-RM1 |
Non-return valve |
Included in NIBE FLM |
||
-AZ10-RN11 |
Control valve |
Included in NIBE FLM |
||
-AZ10-RN1 |
Trim valve |
Included in NIBE FLM |
||
0 |
Exhaust air module |
NIBE F135 |
067 075 |
|
0 |
Exhaust air module |
NIBE S135 |
067 075 |
|
-CL11 |
Pool system |
|||
-CL11-AA25 |
AXC module, pool |
|||
-CL11-BT25 |
External supply temperature sensor |
|||
-CL11-BT51 |
Pool sensor |
|||
-CL11-EP5 |
Exchanger, pool |
|||
-CL11-GP9 |
Circulation pump, pool |
|||
-CL11-HQ4 |
Particle filter, pool |
|||
-CL11-QN19 |
Three way valve, pool |
|||
-CL11-RM1 |
Non-return valve, pool |
|||
-CL12 |
Pool system 2 |
|||
-CL12-AA25 |
AXC module |
|||
-CL12-BT25 |
External supply temperature sensor |
|||
-CL12-BT51 |
Pool sensor |
|||
-CL12-EP5 |
Exchanger, pool |
|||
-CL12-GP9 |
Circulation pump, pool |
|||
-CL12-GP12 |
Charge pump, pool |
Included in POOL 310 |
||
-CL12-HQ4 |
Particle filter, pool |
|||
-CL12-QN19 |
Three way valve, pool |
See the valve’s manual for a port description. |
||
-CP1 |
Storage tank |
|||
-CP1-FQ1 |
Separable valve connector |
|||
-CP1-RN60.1 |
Trim valve |
|||
-CP1-RN60.2 |
Trim valve |
|||
-CP2-RN60.1 |
Trim valve |
|||
-CP2-RN60.2 |
Trim valve |
|||
-CP2-RN60 |
Trim valve |
|||
-CP2-RN61 |
Trim valve |
|||
-CP2 |
Water heater |
|||
-CP2-FQ1 |
Thermal mixing valve |
Part no. 624 922 |
||
-CP4 |
Additional water heater |
|||
-CP10.4 |
Tanks |
|||
-CP10.4 |
Storage tank |
UKV 20 |
Size varies depending on heat pump and system volume |
|
-CP10.5 |
Storage tank |
UKV 20 |
Size varies depending on heat pump and system volume |
|
-CP10.6 |
Storage tank |
UKV 20 |
Size varies depending on heat pump and system volume |
|
-CP10.7 |
Storage tank |
UKV 20 |
Size varies depending on heat pump and system volume |
|
-EB1 |
Step-controlled additional heat/electric boiler |
|||
-EB1-AA25 |
AXC module |
Included in AXC 50 |
067 060 |
|
-EB1-BT25 |
Supply temperature sensor, heating medium, external |
Included in AXC 50 |
||
-EB1-BT52 |
Boiler sensor |
Included in AXC 50 |
||
-EB1-CM5 |
Closed expansion vessel, heating medium |
|||
-EB1-EP7 |
District heating exchanger |
|||
-EB1-FL2 |
Safety valve, heating medium |
|||
-EB1-GP10 |
Circulation pump, heating medium external |
|||
-EB1-QM40 |
Shut-off valve |
|||
-EB1-QM41 |
Shut-off valve |
|||
-EB1-QN11 |
Shuttle valve |
See the valve’s manual for a port description. |
||
-EB1-RM5 |
Non-return valve |
|||
-EB1-RN11 |
Control valve |
|||
-EB2 |
External electrical backup |
|||
-EB3 |
Immersion heater in tank |
with junction box K11 |
IU 3 kW: 695 20 30 IU 6 kW: 695 20 71 IU 9 kW: 695 20 97 K11: 695 22 38 |
|
-KA1 |
Auxiliary relay |
HR 10 |
||
-EB15 |
Indoor module |
F1345/F1355 |
||
-EB15-BT1 |
Outside sensor |
Included in F1345/F1355 |
||
-EB15-BT25 |
External supply temperature sensor |
Included in AXC 50 |
||
-EM1 |
Shunt controlled additional heat |
|||
-EM1-AA25 |
AXC module |
Included in AXC 50 |
067 060 |
|
-EM1-QN11 |
Shunt valve for additional heat |
|||
-EM1-BT52 |
Boiler sensor |
Included in AXC 50 |
||
-EM1-BT25 |
Supply temperature sensor, heating medium, external |
Included in AXC 50 |
||
-EM1-GP10 |
External heating medium pump |
|||
-EM1/EB1 |
Electric boiler, wood boiler, pellet boiler, oil boiler or district heating |
|||
-EM1/EB1-GP10 |
Circulation pump |
|||
-EP1 |
District heating |
|||
-EP1-AA25 |
AXC module |
Included in AXC 50 |
067 060 |
|
-EP1-BT25 |
External supply temperature sensor |
Included in AXC 50 |
||
-EP1-BT52 |
Boiler sensor |
Included in AXC 50 |
||
-EP1-CM5 |
Closed expansion vessel, heating medium |
|||
-EP1-EP3 |
District heating exchanger, hot water |
|||
-EP1-EP7 |
District heating exchanger |
|||
-EP1-FL2 |
Safety valve, heating medium |
|||
-EP1-QN11 |
Mixing valve, addition |
See the valve’s manual for a port description. |
||
-EP1-RM1 |
Non-return valve |
|||
-EP10 |
Shunt controlled brine |
|||
-EP10-AA25 |
AXC module |
Included in AXC 50 |
067 060 |
|
-EP10-BT26 |
Temperature sensor, brine in |
Included in AXC 50 |
||
-EP10-QN41 |
Shunt valve, brine temperature |
See the valve’s manual for a port description. |
||
-EP10-EP10 |
Heat exchanger |
|||
-EP12 |
Ground water system |
|||
-EP12-AA25 |
AXC module, groundwater |
Included in AXC 50 |
067 060 |
|
-EP12-EP4 |
Groundwater exchanger |
|||
-EP12-GP3 |
Circulation pump, groundwater |
|||
-EP12-HQ40 |
Particle filter, groundwater |
|||
-EP21 |
Heating system 2 |
false |
067 287 / 067 288 |
|
-EP21-AA25 |
AXC module, heating system 2 |
Included in false |
||
-EP21-BT2 |
Supply temperature sensor, heating system 2 |
Included in false |
||
-EP21-BT3 |
Return line sensor, heating system 2 |
Included in false |
||
-EP21-GP10 |
Circulation pump, heating system 2 |
Included in false |
||
-EP21-QN25 |
Shunt valve, heating system 2 |
Included in false See the valve’s manual for a port description. |
||
-EP22 |
Heating system 3 |
false |
067 287 / 067 288 |
|
-EP22-AA25 |
AXC module, heating system 3 |
Included in false |
||
-EP22-BT2 |
Supply temperature sensor, heating system 3 |
Included in false |
||
-EP22-BT3 |
Return line sensor, heating system 3 |
Included in false |
||
-EP22-GP20 |
Circulation pump, heating system 3 |
Included in false |
||
-EP22-QN25 |
Shunt valve, heating system 3 |
Included in false See the valve’s manual for a port description. |
||
-EP30 |
Solar heating system |
SCA 35 |
067 245 |
|
-EP30-AA25 |
AXC module |
Included in SCA 35 |
||
-EP8 |
Solar panels |
|||
-EP30-EP9 |
Exchanger, solar |
|||
-EP30-GP10 |
Circulation pump |
|||
-EP44 |
Cooling system 1 |
067 287 / 067 288 |
||
-EP44-AA25 |
AXC module, cooling system 1 |
|||
-EP44-BT2 |
Supply temperature sensor, cooling system 1 |
|||
-EP44-BT3 |
Return line sensor, cooling system 1 |
|||
-EP44-BT64 |
Flow temperature sensor, cooling |
|||
-EP44-BT65 |
Return line sensor, cooling |
|||
-EP44-GP10 |
Circulation pump, cooling system 1 |
|||
-EP44-QN18 |
Shunt valve, cooling system 1 |
See the valve’s manual for a port description. |
||
-EP44-RM1 |
Non-return valve |
|||
-EP25 |
Passive cooling system |
false |
067 296 |
|
-EP25-AA25 |
AXC module, cooling |
Included in false |
||
-EP25-BT64 |
Temperature sensor, cooling flow line |
Included in false |
||
-EP25-BT65 |
Temperature sensor, cooling return line |
Included in false |
||
-EP25-EP13 |
Supply air coil/fan coil |
|||
-EP25-GP13 |
Circulation pump, cooling |
Included in false |
||
-EP25-QN18 |
Mixing valve, cooling |
Included in false See the valve’s manual for a port description. |
||
-EP25-RM1 |
Non-return valve |
|||
-EQ1 |
Active cooling. |
false |
067 195 |
|
-EQ1-AA25 |
AXC module, cooling |
Included in false |
||
-EQ1-BT57 |
Temperature sensor, collector |
Included in false |
||
-EQ1-BT64 |
Flow temperature sensor, cooling |
Included in false |
||
-EQ1-BT75 |
Temperature sensor, flow line after heat dump |
|||
-EQ1-CP10.2 |
Volume vessel, cooling |
UKV 200/UKV 300 |
080321 / 080330 |
Condensation-insulated vessel for cooling |
-EQ1-EP6 |
Heat exchanger |
|||
-EQ1-GP10 |
Circulation pump |
Included in false |
||
-EQ1-GP12 |
Circulation pump |
Included in false |
||
-EQ1-GP14 |
Circulation pump for heat dump |
|||
-EQ1-GP20 |
Circulation pump, heat dump |
|||
-EQ1-QM40.1 |
Shut-off valve |
|||
-EQ1-QM40.2 |
Shut-off valve |
|||
-EQ1-QN12 |
Reversing valve, cooling |
See the valve’s manual for a port description. |
||
-EQ1-QN18 |
Mixing valve, cooling dump |
See the valve’s manual for a port description. |
||
-EQ1-QN36 |
Mixing valve, heat dump |
See the valve’s manual for a port description. |
||
-EQ1-RM1 |
Non-return valve, heat dump |
|||
-EQ2 |
Heat dump |
|||
-EQ2-EP6 |
Heat exchanger |
|||
-EQ2-GP14 |
Circulation pump for heat dump |
|||
-EQ2-GP10 |
Circulation pump, heat dump |
|||
-EQ2-QN36 |
Mixing valve, heat dump |
See the valve’s manual for a port description. |
||
-EZ2 |
Domestic hot water module |
Cetetherm AquaEfficiency |
Cetetherm AB |
|
-QZ1 |
Hot water circulation (HWC) |
|||
-QZ1-AA25 |
AXC module |
Included in AXC 50 |
067 060 |
|
-QZ1-BT70 |
Supply temperature sensor, HWC |
Included in AXC 50 |
||
-QZ1-BT82 |
Return line sensor, HWC |
Included in AXC 50 |
||
-QZ1-FQ3 |
Mixer valve, HWC |
|||
-QZ1-GP11 |
Circulation pump, HWC |
|||
-QZ1-QN2 |
4-way valve, HWC |
See the valve’s manual for a port description. |
||
-QZ1-RM1 |
Non-return valve, HWC |
|||
-QZ1-RN1 |
Trim valve, HWC |
|||
-QZ1-RN4 |
Trim valve, HWC |
|||
-QZ20 |
Filling kit |
KB 25/ KB 32 |
KB 25 (max. 12 kW), KB 32 (max. 30 kW) |
|
-XL27 |
Connection for filling brine |
|||
-XL28 |
Connection for filling brine |
|||
-RN1.1 |
Miscellaneous |
|||
-AA25 |
Accessory card |
AXC 50 |
Required if the groundwater pump or hot water circulation pump is to be connected to F1345/F1355 at the same time as the common alarm. The relay outputs on the accessory board can have a max. load of 2 A (230 V) in total. |
|
-BP5 |
Pressure gauge, heating medium |
|||
-BP6 |
Pressure gauge, brine |
|||
-CM1 |
Closed expansion vessel, heating medium |
|||
-CM2 |
Level vessel, brine |
Included in F1345/F1355 |
Level vessel in open system |
|
-CM3 |
Expansion vessel, brine |
Expansion vessel in closed system |
||
-CM4 |
Expansion vessel, hot water |
|||
-CP10.1 |
Buffer vessel |
UKV 100/ UKV 200/ UKV 300/ UKV 500 |
Size varies depending on heat pump and system volume |
|
-CP10.2 |
Volume vessel |
UKV 200/300 cooling |
Condensation-insulated vessel for cooling |
|
-CP10.3 |
Buffer vessel |
UKV 100/200/300/500 |
Size varies depending on heat pump and system volume |
|
-FL1 |
Safety valve, hot water |
|||
-FL2 |
Safety valve, heating medium |
|||
-FL3 |
Safety valve, brine |
Included in F1345/F1355 |
||
-FQ1 |
Mixing valve |
Thermal |
||
-HQ1 |
Particle filter, brine |
Included in F1355 |
||
-HQ2 |
Particle filter, brine |
Included in F1355 |
||
-HQ3 |
Particle filter, heating medium |
Included in F1355 |
||
-HQ4 |
Particle filter, heating medium |
Included in F1355 |
||
-RM1 |
Non-return valve |
|||
-RM2 |
Non-return valve |
|||
-RM3 |
Non-return valve |
|||
-RN1.1 |
Trim valve |
|||
-RN1.2 |
Trim valve |
|||
-RN1.3 |
Trim valve |
|||
-RN2.1 |
Trim valve |
|||
-RN2.2 |
Trim valve |
|||
-RN3.1 |
Trim valve |
|||
-RN3.2 |
Trim valve |
|||
-RN4.1 |
Trim valve |
|||
-RN4.2 |
Trim valve |
|||
-RN5.1 |
Trim valve |
|||
-RN5.2 |
Trim valve |
|||
-QM1 |
Drain valve, heating medium |
|||
-QM30 |
Shut-off valve, hot water |
|||
-QM34 |
Shut off valve, brine out |
|||
-QN17 |
Pressure reduction valve |
|||
-WM3 |
Tundish, cold water |
Included in F1345/F1355 |
||
-WM4 |
Tundish, T&P valve |
Included in F1345/F1355 |
Designations according to standard EN 81346-2.