Protective and safety equipment as well as components that facilitate servicing (e.g. non-return valves, safety valves, overflow valves, shut-off valves) must be installed in accordance with national regulations and standards.
The compressors in a F1345 are of the on/off type. The compressor’s full power is routed to heating, hot water, cooling or pool heating, where applicable. If the power is not sufficient for heating, additional heating engages automatically.
The compressors in a F1355 consist of one on/off type and one inverter-controlled compressor. The compressor power is adjusted based on the demand and routed to heating, hot water, cooling or pool heating, where applicable. If the power is not sufficient for the heating demand, additional heating engages automatically.
F1345/F1355 is supplied with a heating control system, which means that the heating supply to the house takes place according to selected settings. For more information about heat production, see the Installer Manual.
Multiple heat pumps can be interconnected, by selecting one heat pump as the master and the others as slaves. The heat pump is always delivered as the master heat pump, and up to 8 subordinate heat pumps can be connected to it and supply up to 540 kW (with 9 x F1345-60 kW) in the same system. In systems with several heat pumps, each pump is given a unique name. External temperature sensors and control signals must be connected solely to the primary heat pump, except for external control of the compressor module and reversing valve(s) (QN10), which can be connected one to each heat pump.
With the accessory AXC 50 (one for each accessory function that will be used), an external heating medium pump (for the climate system) can be connected to the heat pump, if the alarm relay (AUX output) is activated for another function. If the AUX output cannot be used for an external circulation pump, the function can be found in:
addition
shunt-controlled additional heat
pool
If there is a large pressure drop over the brine side, an external brine pump may be required.
This function requires the ECS 40/41 accessory. Shunt valve, supply and return line sensors and circulation pump are connected to a second heating circuit with a lower temperature demand (e.g. underfloor heating system). The temperature in the extra heating system is in accordance with the selected curve slope and offset setting. Up to 8 extra heating systems can be connected to the installation, and each extra heating system must operate at a lower temperature than the system from which it is shunted. For further information, see the Installer Manual for the accessory.
For enhanced hot water.
Exhaust air recovery means that the heat pump recovers heat from the exhaust air and supplies it to the heating system.
This function requires the NIBE FLM accessory. The integrated fan in NIBE FLM extracts air from the various areas of the house to the recovery unit. Here, the heat energy is transferred to the installation, thereby increasing the temperature and raising the installation’s coefficient of performance.
For more information, see the manual for the ventilation.
With AXC 50 a ground water pump can be connected to the heat pump if the software controlled output (AUX output) is used for something else.
This connection enables the use of ground water as heat source. The ground water is pumped up to an intermediate heat exchanger. An intermediate heat exchanger is used to protect the heat pump's exchanger from dirt and freezing. The water is released into a buried filtration unit or a drilled well.
The ground water pump runs at the same time as the brine pump.
This function requires the AXC 50 accessory. The cooling system is connected to the heat pump brine circuit, through which cooling is supplied from the collector via the circulation pump and the shunt valve.
When cooling is required (activated from the outdoor temperature sensor and any room sensor), the shunt valve and the circulation pump are activated.
The shunt valve regulates so that the cooling sensor reaches the current set point value corresponding to the outdoor temperature and the set min. value for the cooling temperature (to prevent condensation).
This function requires the ACS 45 accessory. The cooling system is connected to the heat pump’s brine circuit, through which cooling is supplied from the collector via circulation pump and shunt valve.
When cooling is required (activated from the outdoor temperature sensor and any room sensor), the shunt valve and the circulation pump are activated.
This function permits the distribution of heat and cooling independently of each other.
POOL 40 is an accessory that enables pool heating with a compressor in your installation.
For further information, see the Installer Manual for the accessory.
During pool operation and hot water production, you can choose which of the compressors will be responsible for operation. More compressor selections can be made. An example with one or two compressors for the main heat pump is shown here.
Additional heat that requires the AXC 50 accessory. AXC 50 via a control signal, can control step-controlled additional heat. The additional heat is used for heat production.
For further information, see the Installer Manual for the accessory.
Additional heat that requires the AXC 50 accessory. AXC 50 via a control signal, can control additional heat, which can also be prioritised. The additional heat is used for heat production.
For further information, see the Installer Manual for the accessory.
This function enables district heating additional heat to assist with heating.
For more information about district heating additional heat, see its manual.
This function enables district heating additional heat to produce both heat and hot water, including hot water circulation.
For more information about district heating additional heat, see its manual.
This connection makes it possible to control a shunt valve that regulates the incoming brine temperature.
The heat pump controls a shunt valve (QN41) to limit the maximum incoming brine temperature via temperature sensor (BT26). If the sensor registers a value above the maximum set temperature, the shunt valve is closed to reduce the mix of incoming brine.
The function is only active when a compressor in the system is running and requires the accessory AXC 50.
A buffer vessel is an accumulator tank that is suitable for connection to a heat pump or another external heat source, and can have several different applications. It can also be used during external control of the heating system.
For further information, see the Installer Manual for the accessory.
A circulation pump can be controlled by F1345/F1355 to circulate the hot water. The circulating water must have a temperature that prevents bacterial growth and scalding, and national standards must be satisfied. See the appropriate Installer Manual for more information.
The hot water is enhanced with district heating, which is used with hot water circulation.
In the event of excess heat, this is dumped to the collector or outdoor air via a fan battery outdoors.
Designation |
Name |
Specification |
Part No. |
Comments |
---|---|---|---|---|
-AA35-BT1 |
Outside sensor |
Included in F1345/F1355 Modbus: 40004 |
||
-AA35-BT6 |
Controlling hot water sensor |
Included in F1345/F1355 Modbus: 40014 |
||
-AA35-BT7 |
Display hot water sensor |
Included in F1345/F1355 Modbus: 40013 |
||
-AA35-BT25 |
External supply temperature sensor |
Included in F1345/F1355 Modbus: 40071 |
||
-AA35-BT63 |
External supply temperature sensor before QN10 |
Modbus: 40121 |
||
-AA35-BT71 |
External return line sensor |
Included in F1345/F1355 Modbus: 40152 |
||
-AA35-GP10 |
External heating medium pump |
Modbus: 43189 |
||
-AA35-GP12.1 |
Charge pump for EB101 |
NIBE CPD 11 Modbus: 44396 |
067 321 / 067 320 |
|
-AA35-GP12.2 |
Charge pump for EB102 |
NIBE CPD 11 Modbus: 44395 |
067 321 / 067 320 |
|
-AA35-GP12.3 |
Charge pump for EB103 |
NIBE CPD 11 Modbus: 44394 |
067 321 / 067 320 |
|
-AA35-GP12.4 |
Charge pump for EB104 |
NIBE CPD 11 Modbus: 44393 |
067 321 / 067 320 |
|
-AA35-QN10 |
Reversing valve, heating/hot water |
See the valve’s manual for a port description. |
||
-EB100 |
Heat pump system (master unit) |
F1345/F1355 |
||
-EB100F1355 |
Heat pump system (master unit) |
F1355 |
||
-EB100F1330 |
Heat pump system (master unit) |
F1345-24/30 |
||
-EB100F1360 |
Heat pump system (master unit) |
F1345-40/60 |
||
-EP14 |
Cooling module |
See the Installer Manual for more information about the relevant cooling module. |
||
-EP15 |
Cooling module |
See the Installer Manual for more information about the relevant cooling module. |
||
-BT6 |
Controlling hot water sensor |
Included in F1345/F1355 Modbus: 40014 |
||
-EB100-BT6 |
Controlling hot water sensor |
Included in F1345/F1355 Modbus: 40014 |
||
-EB100-BT7 |
Display hot water sensor |
Included in F1345/F1355 Modbus: 40013 |
||
-BT7 |
Display hot water sensor |
Included in F1345/F1355 Modbus: 40013 |
||
-EB100-BT25 |
External supply temperature sensor |
Included in F1345/F1355 Modbus: 40071 |
||
-EB100-BT71 |
External return line sensor |
Included in F1345/F1355 Modbus: 40152 |
||
-EB100-CM4 |
Expansion vessel, hot water |
Included in F1345/F1355 |
||
-EB100-FL1 |
Safety valve, hot water |
Included in F1345/F1355 |
||
-EB100-FL5 |
T&P valve |
Included in F1345/F1355 |
||
-EB100-FL6 |
Vacuum valve |
Included in F1345/F1355 |
||
-EB100-FQ1 |
Mixing valve |
Included in F1345/F1355 |
||
-EB100-QN17 |
Pressure reduction valve |
Included in F1345/F1355 |
||
-EB100-QM30 |
Shut-off valve |
|||
-EB100-RM1 |
Non-return valve |
|||
-EB100-WM3.1 |
Tundish, cold water |
Included in F1345/F1355 |
||
-EB100-WM3.2 |
Tundish, T&P valve |
Included in F1345/F1355 |
||
-EB100-GP7 |
External brine pump |
|||
-EB100-GP10 |
External heating medium pump |
Modbus: 43189 |
||
-EB100-QN10 |
Reversing valve, heating/hot water |
See the valve’s manual for a port description. |
||
-BT1 |
Outside sensor |
Included in F1345/F1355 Modbus: 40004 |
||
-BT25 |
External supply temperature sensor |
Modbus: 40071 |
||
-EP4 |
Heat exchanger, groundwater |
|||
-FL10 |
Safety valve, brine |
|||
-FL10-0 |
Safety valve, brine |
|||
-FL11-0 |
Safety valve, brine |
|||
-FL12-0 |
Safety valve, heating medium |
|||
-FL13-0 |
Safety valve, heating medium |
|||
-HQ1-F1360 |
Particle filter, brine |
Included in F1345-40/60 |
||
-HQ1-F1330 |
Particle filter, brine |
Included in F1345-24/30 |
||
-HQ2-F1360 |
Particle filter, brine |
Included in F1345-40/60 |
||
-HQ2-F1330 |
Particle filter, brine |
Included in F1345-24/30 |
||
-HQ3-F1360 |
Particle filter, heating medium |
Included in F1345-40/60 |
||
-HQ3-F1330 |
Particle filter, heating medium |
Included in F1345-24/30 |
||
-HQ4-F1360 |
Particle filter, heating medium |
Included in F1345-40/60 |
||
-HQ4-F1330 |
Particle filter, heating medium |
Included in F1345-24/30 |
||
-GP16-0 |
Circulation pump, brine |
Included in F1345-24/30 40/60 Modbus: 43439 |
||
-QN11 |
Shuttle valve |
|||
-QM12 |
Filling valve, brine |
|||
-QM21 |
Vent valve, brine |
|||
-QM31 |
Shut-off valve, heating medium supply line |
|||
-QM32 |
Shut-off valve, heating medium return line |
|||
-QM33 |
Shut-off valve, brine in |
|||
-QM40 |
Shut-off valve |
|||
-QM42 |
Shut-off valve, brine in |
|||
-QM50-0 |
Shut off valve, brine |
|||
-QM51-0 |
Shut off valve, brine |
|||
-QM52-0 |
Shut off valve, brine |
|||
-QM53-0 |
Shut off valve, brine |
|||
-QM54-0 |
Shut-off valve, heating medium |
|||
-QM55-0 |
Shut-off valve, heating medium |
|||
-QM56-0 |
Shut-off valve, heating medium |
|||
-QM57-0 |
Shut-off valve, heating medium |
|||
-QZ2 |
Filterball, heating medium |
Included in F1355 |
The F1345-24/30 includes a particle filter, which should be supplemented with a shut-off valve. |
|
-QZ2.1-0 |
Filterball, heating medium |
Included in F1355 |
||
-QZ2.2-0 |
Filterball, heating medium |
Included in F1355 |
||
-QZ2.3-0 |
Filterball, heating medium |
Included in F1355 |
||
-QZ2.4-0 |
Filterball, heating medium |
Included in F1355 |
||
-QZ3 |
Filterball, brine |
Included in F1355 |
||
-QZ4 |
Filterball, heating medium |
Included in F1355 |
The F1345-24/30 includes a particle filter, which should be supplemented with a shut-off valve. |
|
-QZ5 |
Filterball, heating medium |
Included in F1355 |
The F1345-24/30 includes a particle filter, which should be supplemented with a shut-off valve. |
|
-RM10-F1360 |
Non-return valve |
|||
-RM10-F1330 |
Non-return valve |
Included in F1345-24/30 |
||
-RM10-F1355 |
Non-return valve |
Included in F1355 |
||
-RM11-F1360 |
Non-return valve |
Included in F1345-40/60 |
||
-RM11-F1330 |
Non-return valve |
Included in F1345-24/30 |
||
-RM11-F1355 |
Non-return valve |
Included in F1355 |
||
-RM12-F1360 |
Non-return valve |
Included in F1345-40/60 |
||
-RM12-F1330 |
Non-return valve |
Included in F1345-24/30 |
||
-RM12-F1355 |
Non-return valve |
Included in F1355 |
||
-RM13-F1360 |
Non-return valve |
Included in F1345-40/60 |
||
-RM13-F1330 |
Non-return valve |
Included in F1345-24/30 |
||
-RM13-F1355 |
Non-return valve |
Included in F1355 |
||
-RN20 |
Trim valve |
|||
-RN21 |
Trim valve |
|||
-EB10011xx |
Heat pump system (master unit) |
F1355 |
||
-EB10012xx |
Heat pump system (master unit) |
F1345-24/30 |
||
-EB10013xx |
Heat pump system (master unit) |
F1345-40/60 |
||
-BT111xx |
Outside sensor |
Included in F1355 Modbus: 40004 |
||
-BT112xx |
Outside sensor |
Included in F1345-24/30 Modbus: 40004 |
||
-BT113xx |
Outside sensor |
Included in F1345-40/60 Modbus: 40004 |
||
-QZ311xx |
Filterball, brine |
Included in F1355 |
||
-QZ312xx |
Filterball, brine |
Included in F1345-24/30 |
||
-EB100-BT2511xx |
External supply temperature sensor |
Included in F1355/F1345/F1355 Modbus: 40071 |
||
-EB100-BT7111xx |
External return line sensor |
Included in F1355/F1345/F1355 Modbus: 40152 |
||
-EB100-QZ211xx |
Filterball, heating medium |
Included in F1355 |
||
-EB100-QZ212xx |
Filterball, heating medium |
Included in F1345-24/30 |
||
-EB101F1355 |
Heat pump system 1 |
F1355 |
||
-EB101F1330 |
Heat pump system 1 |
F1345-24/30 |
||
-EB101F1360 |
Heat pump system 1 |
F1345-40/60 |
||
-EB101 |
Heat pump system 1 |
|||
-GP16-1 |
Circulation pump, brine |
Included in F1345-24/30 40/60 Modbus: 43439 |
||
-EB101-FL10 |
Safety valve, brine |
|||
-FL10-1 |
Safety valve, brine |
|||
-FL11-1 |
Safety valve, brine |
|||
-FL12-1 |
Safety valve, heating medium |
|||
-FL13-1 |
Safety valve, heating medium |
|||
-HQ1-1361 |
Particle filter, brine |
Included in F1345-40/60 |
||
-HQ1-F1330-1 |
Particle filter, brine |
Included in F1345-24/30 |
||
-HQ2-1362 |
Particle filter, brine |
Included in F1345-40/60 |
||
-HQ2-F1330-1 |
Particle filter, brine |
Included in F1345-24/30 |
||
-HQ3-1362 |
Particle filter, heating medium |
Included in F1345-40/60 |
||
-HQ3-F1330-1 |
Particle filter, heating medium |
Included in F1345-24/30 |
||
-HQ4-1362 |
Particle filter, heating medium |
Included in F1345-40/60 |
||
-HQ4-F1330-1 |
Particle filter, heating medium |
Included in F1345-24/30 |
||
-EB101-QM1 |
Drain valve, heating medium |
|||
-EB101-QM40 |
Shut-off valve, heating medium |
|||
-QM50-1 |
Shut off valve, brine |
|||
-QM51-1 |
Shut off valve, brine |
|||
-QM52-1 |
Shut off valve, brine |
|||
-QM53-1 |
Shut off valve, brine |
|||
-QM54-1 |
Shut-off valve, heating medium |
|||
-QM55-1 |
Shut-off valve, heating medium |
|||
-QM56-1 |
Shut-off valve, heating medium |
|||
-QM57-1 |
Shut-off valve, heating medium |
|||
-EB101-QZ2 |
Filterball, heating medium |
Included in F1355 |
||
-QZ2.1-1 |
Filterball, brine |
Included in F1355 |
||
-QZ2.2-1 |
Filterball, brine |
Included in F1355 |
||
-QZ2.3-1 |
Filterball, heating medium |
Included in F1355 |
||
-QZ2.4-1 |
Filterball, heating medium |
Included in F1355 |
||
-EB101-RM1 |
Non-return valve, heating medium |
|||
-RM10-F1361 |
Non-return valve |
|||
-RM10-F1330-1 |
Non-return valve |
Included in F1345-24/30 |
||
-RM10-F1355-1 |
Non-return valve |
Included in F1355 |
||
-RM11-F1361 |
Non-return valve |
Included in F1345-40/60 |
||
-RM11-F1330-1 |
Non-return valve |
Included in F1345-24/30 |
||
-RM11-F1355-1 |
Non-return valve |
Included in F1355 |
||
-RM12-F1361 |
Non-return valve |
Included in F1345-40/60 |
||
-RM12-F1330-1 |
Non-return valve |
Included in F1345-24/30 |
||
-RM12-F1355-1 |
Non-return valve |
Included in F1355 |
||
-RM13-F1361 |
Non-return valve |
Included in F1345-40/60 |
||
-RM13-F1330-1 |
Non-return valve |
Included in F1345-24/30 |
||
-RM13-F1355-1 |
Non-return valve |
Included in F1355 |
||
-EB102 |
Heat pump system 2 |
|||
-EB102F1355 |
Heat pump system 2 |
F1355 |
||
-EB102F1330 |
Heat pump system 2 |
F1345-24/30 |
||
-EB102F1360 |
Heat pump system 2 |
F1345-40/60 |
||
-GP16-2 |
Circulation pump, brine |
Included in F1345-24/30 40/60 Modbus: 43439 |
||
-EB102-FL10 |
Safety valve, heating medium |
|||
-FL10-2 |
Safety valve, brine |
|||
-FL11-2 |
Safety valve, brine |
|||
-FL12-2 |
Safety valve, heating medium |
|||
-FL13-2 |
Safety valve, heating medium |
|||
-HQ1-F1362 |
Particle filter, brine |
Included in F1345-40/60 |
||
-HQ1-F1330-2 |
Particle filter, brine |
Included in F1345-24/30 |
||
-HQ2-F1362 |
Particle filter, brine |
Included in F1345-40/60 |
||
-HQ2-F1330-2 |
Particle filter, brine |
Included in F1345-24/30 |
||
-HQ3-F1362 |
Particle filter, heating medium |
Included in F1345-40/60 |
||
-HQ3-F1330-2 |
Particle filter, heating medium |
Included in F1345-24/30 |
||
-HQ4-F1362 |
Particle filter, heating medium |
Included in F1345-40/60 |
||
-HQ4-F1330-2 |
Particle filter, heating medium |
Included in F1345-24/30 |
||
-EB102-QM1 |
Drain valve, heating medium |
|||
-EB102-QM40 |
Shut-off valve, heating medium |
|||
-QM50-2 |
Shut off valve, brine |
|||
-QM51-2 |
Shut off valve, brine |
|||
-QM52-2 |
Shut off valve, brine |
|||
-QM53-2 |
Shut off valve, brine |
|||
-QM54-2 |
Shut-off valve, heating medium |
|||
-QM55-2 |
Shut-off valve, heating medium |
|||
-QM56-2 |
Shut-off valve, heating medium |
|||
-QM57-2 |
Shut-off valve, heating medium |
|||
-EB102-QZ2 |
Filterball, heating medium |
Included in F1355 |
||
-QZ2.1-2 |
Filterball, brine |
Included in F1355 |
||
-QZ2.2-2 |
Filterball, brine |
Included in F1355 |
||
-QZ2.3-2 |
Filterball, heating medium |
Included in F1355 |
||
-QZ2.4-2 |
Filterball, heating medium |
Included in F1355 |
||
-EB102-RM1 |
Non-return valve, heating medium |
|||
-RM10-F1362 |
Non-return valve |
|||
-RM10-F1330-2 |
Non-return valve |
Included in F1345-24/30 |
||
-RM10-F1355-2 |
Non-return valve |
Included in F1355 |
||
-RM11-F1362 |
Non-return valve |
Included in F1345-40/60 |
||
-RM11-F1330-2 |
Non-return valve |
Included in F1345-24/30 |
||
-RM11-F1355-2 |
Non-return valve |
Included in F1355 |
||
-RM12-F1362 |
Non-return valve |
Included in F1345-40/60 |
||
-RM12-F1330-2 |
Non-return valve |
Included in F1345-24/30 |
||
-RM12-F1355-2 |
Non-return valve |
Included in F1355 |
||
-RM13-F1362 |
Non-return valve |
Included in F1345-40/60 |
||
-RM13-F1330-2 |
Non-return valve |
Included in F1345-24/30 |
||
-RM13-F1355-2 |
Non-return valve |
Included in F1355 |
||
-EB103 |
Heat pump system 3 |
|||
-EB103-AA25 |
AXC module |
Included in AXC 50 |
067 304 |
|
-EB103-FL10 |
Safety valve, heating medium |
|||
-EB103-QM1 |
Drain valve, heating medium |
|||
-EB103-QM40 |
Shut-off valve, heating medium |
|||
-EB103-QZ2 |
Filterball, heating medium |
Included in F1355 |
||
-EB103-RM1 |
Non-return valve, heating medium |
|||
-EB104 |
Heat pump system 4 |
|||
-EB104-FL10 |
Safety valve, heating medium |
|||
-EB104-QM1 |
Drain valve, heating medium |
|||
-EB104-QM40 |
Shut-off valve, heating medium |
|||
-EB104-QZ2 |
Filterball, heating medium |
Included in F1355 |
||
-EB104-RM1 |
Non-return valve, heating medium |
|||
XL |
XL connections |
|||
1 |
Heating medium connection, supply |
|||
XL1 |
Heating medium connection, supply |
|||
2 |
Heating medium connection, return |
|||
XL2 |
Heating medium connection, return |
|||
3 |
Cold water connection |
|||
4 |
Hot water connection |
|||
5 |
Hot water circulation connection |
|||
6 |
Brine connection, supply |
|||
7 |
Brine connection, return |
|||
8 |
Docking connection, supply |
|||
9 |
Docking connection, return |
|||
13 |
Solar heat connection, supply |
|||
14 |
Solar heat connection, return |
|||
18 |
Docking connection, supply |
|||
19 |
Docking connection, return |
|||
29 |
T&Pvalve |
|||
30 |
Expansion vessel connection |
|||
39 |
Docking connection, pool |
|||
-AZ10.1 |
Exhaust air recovery 1 |
|||
-AZ10-GP2 |
Circulation pump, exhaust air recovery |
|||
-AZ10-RM20 |
Non-return valve, exhaust air recovery |
|||
-AZ10-RM1 |
Non-return valve, exhaust air recovery |
|||
-AZ10-RN1 |
Trim valve, exhaust air recovery |
|||
-RN1 |
Trim valve |
|||
-AZ10.2 |
Exhaust air recovery 2 |
|||
-AZ10.3 |
Exhaust air recovery 3 |
|||
-AZ10 |
Exhaust air module |
NIBE FLM |
067 627 |
|
-AZ10-RM1 |
Non-return valve |
Included in NIBE FLM |
||
-AZ10-RN11 |
Control valve |
Included in NIBE FLM |
||
-AZ10-RN1 |
Trim valve |
Included in NIBE FLM |
||
0 |
Exhaust air module |
NIBE F135 |
067 075 |
|
0 |
Exhaust air module |
NIBE S135 |
067 075 |
|
-CL11 |
Pool system |
POOL 40 |
067 062 |
|
-CL11-AA25 |
AXC module, pool |
Included in POOL 40 |
||
-CL11-BT25 |
External supply temperature sensor |
Included in POOL 40 Modbus: 40071 |
||
-CL11-BT51 |
Pool sensor |
Included in POOL 40 Modbus: 40042 |
||
-CL11-EP5 |
Exchanger, pool |
|||
-CL11-GP9 |
Circulation pump, pool |
Modbus: 44749 |
||
-CL11-GP12 |
Charge pump, pool |
Included in POOL 40 Modbus: 44749 |
||
-CL11-HQ4 |
Particle filter, pool |
|||
-CL11-QN19 |
Three way valve, pool |
Included in POOL 40 Modbus: 43564 |
||
-CL11-RM1 |
Non-return valve, pool |
|||
-CL12 |
Pool system 2 |
POOL 40 |
067 062 |
|
-CL12-AA25 |
AXC module |
Included in POOL 40 |
||
-CL12-BT25 |
External supply temperature sensor |
Included in POOL 40 Modbus: 40071 |
||
-CL12-BT51 |
Pool sensor |
Included in POOL 40 Modbus: 40042 |
||
-CL12-EP5 |
Exchanger, pool |
|||
-CL12-GP9 |
Circulation pump, pool |
Modbus: 44748 |
||
-CL12-GP12 |
Charge pump, pool |
Included in POOL 310 Modbus: 44748 |
||
-CL12-HQ4 |
Particle filter, pool |
|||
-CL12-QN19 |
Three way valve, pool |
Included in POOL 40 Modbus: 43564 See the valve’s manual for a port description. |
||
-CL12-RM1 |
Non-return valve |
Included in POOL 40 |
||
-CP1 |
Storage tank |
|||
-CP1.1 |
Storage tank |
|||
-CP1-CM4 |
Expansion vessel, hot water |
Included in F1345/F1355 |
||
-CP1-FL1 |
Safety valve, hot water |
Included in F1345/F1355 |
||
-CP1-FL5 |
T&P valve |
Included in F1345/F1355 |
||
-CP1-FL6 |
Vacuum valve |
Included in F1345/F1355 |
||
-CP1-FQ1 |
Thermal mixing valve |
|||
-CP1-QN17 |
Pressure reduction valve |
Included in F1345/F1355 |
||
-CP1-QM30 |
Shut-off valve |
|||
-CP1-RM1 |
Non-return valve |
|||
-CP1-WM3.1 |
Tundish, cold water |
Included in F1345/F1355 |
||
-CP1.1-WM3.2 |
Tundish, T&P valve |
Included in F1345/F1355 |
||
-CP1.1-RN1.1 |
Trim valve |
|||
-CP1.1-RN1.2 |
Trim valve |
|||
-CP1.2-RN1.1 |
Trim valve |
|||
-CP1.2-RN1.2 |
Trim valve |
|||
-CP1.2 |
Storage tank |
|||
-RN60 |
Trim valve |
|||
-RN61 |
Trim valve |
|||
-CP2-FQ1 |
Thermal mixing valve |
Part no. 624 922 |
||
-CP4 |
Additional water heater |
|||
-CP10.4 |
Tanks |
|||
-CP10.4 |
Storage tank |
UKV 20 |
Size varies depending on heat pump and system volume |
|
-CP10.5 |
Storage tank |
UKV 20 |
Size varies depending on heat pump and system volume |
|
-CP10.6 |
Storage tank |
UKV 20 |
Size varies depending on heat pump and system volume |
|
-CP10.7 |
Storage tank |
UKV 20 |
Size varies depending on heat pump and system volume |
|
-EB1 |
Step-controlled additional heat/electric boiler |
Modbus: 43091 |
||
-EB1-AA25 |
AXC module |
Included in AXC 50 |
067 060 |
|
-EB1-BT25 |
Supply temperature sensor, heating medium, external |
Included in AXC 50 Modbus: 40071 |
||
-EB1-BT52 |
Boiler sensor |
Included in AXC 50 Modbus: 40070 |
||
-EB1-CM5 |
Closed expansion vessel, heating medium |
|||
-EB1-EP7 |
District heating exchanger |
|||
-EB1-FL2 |
Safety valve, heating medium |
|||
-EB1-GP10 |
Circulation pump, heating medium external |
Modbus: 43189 |
||
-EB1-QM40 |
Shut-off valve |
|||
-EB1-QM41 |
Shut-off valve |
|||
-EB1-QN11 |
Shuttle valve |
See the valve’s manual for a port description. |
||
-EB1-RM5 |
Non-return valve |
|||
-EB1-RN11 |
Control valve |
|||
-EB2 |
External electrical backup |
|||
-EB3 |
Immersion heater in tank |
with junction box K11 |
IU 3 kW: 218 009 IU 6 kW: 218 011 IU 9 kW: 218 003 018 893 |
|
-EB3-QA1 |
Auxiliary relay |
HR 10 |
067 309 |
|
-EB15 |
Indoor module |
F1345/F1355 |
||
-EB15-BT1 |
Outside sensor |
Included in F1345/F1355 Modbus: 40004 |
||
-EB15-BT25 |
External supply temperature sensor |
Included in AXC 50 Modbus: 40071 |
||
-EB15-CM4 |
Expansion vessel, hot water |
|||
-EB15-GP10 |
Circulation pump, heating medium external |
Modbus: 43189 |
||
-EB15-FL1 |
Safety valve, hot water |
|||
-EB15-RM2 |
Non-return valve |
|||
-EB15-QM30 |
Shut-off valve, hot water |
|||
-EB15-WM4 |
Tundish, T&P valve |
Included in F1345/F1355 |
||
-EM1 |
Shunt controlled additional heat |
|||
-EM1-AA25 |
AXC module |
Included in AXC 50 |
067 060 |
|
-EM1-QN11 |
Shunt valve for additional heat |
Modbus: 43098 |
||
-EM1-BT52 |
Boiler sensor |
Included in AXC 50 Modbus: 40070 |
||
-EM1-BT25 |
Supply temperature sensor, heating medium, external |
Included in AXC 50 Modbus: 40071 |
||
-EM1-GP10 |
External heating medium pump |
Modbus: 43189 |
||
-EM1/EB1 |
Electric boiler, wood boiler, pellet boiler, oil boiler or district heating |
|||
-EM1/EB1-GP10 |
Circulation pump |
Modbus: 43189 |
||
-EP1 |
District heating |
|||
-EP1-AA25 |
AXC module |
Included in AXC 50 |
067 060 |
|
-EP1-BT25 |
External supply temperature sensor |
Included in AXC 50 Modbus: 40071 |
||
-EP1-BT52 |
Boiler sensor |
Included in AXC 50 Modbus: 40070 |
||
-EP1-CM5 |
Closed expansion vessel, heating medium |
|||
-EP1-EP3 |
District heating exchanger, hot water |
|||
-EP1-EP7 |
District heating exchanger |
|||
-EP1-FL2 |
Safety valve, heating medium |
|||
-EP1-GP10 |
Circulation pump, heating medium external |
Modbus: 43189 |
||
-EP1-QN11 |
Mixing valve, addition |
See the valve’s manual for a port description. Modbus: 43098 |
||
-EP1-RM1 |
Non-return valve |
|||
-EP1-CT1 |
District heating |
Cetetherm |
||
-EP1-CT2 |
District heating |
Cetetherm |
||
-EP1-CT3 |
District heating |
Cetetherm |
||
-EP10 |
Shunt controlled brine |
|||
-EP10-AA25 |
AXC module |
Included in AXC 50 |
067 060 |
|
-EP10-BT26 |
Temperature sensor, brine in |
Included in AXC 50 Modbus: 40179 |
||
-EP10-QN41 |
Shunt valve, brine |
Modbus: 44778 See the valve’s manual for a port description. |
||
-EP10-EP10 |
Heat exchanger |
|||
-EP12 |
Ground water system |
|||
-EP12-AA25 |
AXC module, groundwater |
Included in AXC 50 |
067 060 |
|
-EP12-EP4 |
Groundwater exchanger |
|||
-EP12-GP3 |
Circulation pump, groundwater |
Modbus: 44756 |
||
-EP12-HQ40 |
Particle filter, groundwater |
|||
-EP21 |
Heating system 2 |
AXC 50 |
067 193 |
|
-EP21-AA25 |
AXC module, heating system 2 |
Included in ECS 40/41 |
||
-EP21-BT2 |
Supply temperature sensor, heating system 2 |
Included in ECS 40/41 Modbus: 40007 |
||
-EP21-BT3 |
Return line sensor, heating system 2 |
Included in ECS 40/41 Modbus: 40129 |
||
-EP21-GP10 |
Circulation pump, heating system 2 |
Modbus: 44746 |
||
-EP21-QN25 |
Shunt valve, heating system 2 |
Modbus: 43095 See the valve’s manual for a port description. |
||
-EP21-RM1 |
Non-return valve |
|||
-EP22 |
Heating system 3 |
AXC 50 |
067 193 |
|
-EP22-AA25 |
AXC module, heating system 3 |
Included in ECS 40/41 |
||
-EP22-BT2 |
Supply temperature sensor, heating system 3 |
Included in ECS 40/41 Modbus: 40006 |
||
-EP22-BT3 |
Return line sensor, heating system 3 |
Included in ECS 40/41 Modbus: 40128 |
||
-EP22-GP10 |
Circulation pump, heating system 3 |
Modbus: 44745 |
||
-EP22-QN25 |
Shunt valve, heating system 3 |
Modbus: 43094 See the valve’s manual for a port description. |
||
-EP22-RM1 |
Non-return valve |
|||
-EP30 |
Solar heating system |
SCA 35 |
067 245 |
|
-EP30-AA25 |
AXC module |
Included in SCA 35 |
||
-EP8 |
Solar panels |
|||
-EP30-EP9 |
Exchanger, solar |
|||
-EP30-GP10 |
Circulation pump |
Modbus: 43183 |
||
-EP44 |
Cooling system 1 |
AXC 50 |
067 193 |
|
-EP44-AA25 |
AXC module, cooling system 1 |
Included in AXC 50 |
||
-EP44-BT2 |
Supply temperature sensor, cooling system 1 |
Modbus: 40007 |
||
-EP44-BT3 |
Return line sensor, cooling system 1 |
Modbus: 40129 |
||
-EP44-BT64 |
Flow temperature sensor, cooling |
Included in AXC 50 Modbus: 40045 |
||
-EP44-BT65 |
Return line sensor, cooling |
Included in AXC 50 Modbus: 40046 |
||
-EP44-GP10 |
Circulation pump, cooling system 1 |
Modbus: 44754 |
||
-EP44-QN18 |
Shunt valve, cooling system 1 |
Modbus: 44278 See the valve’s manual for a port description. |
||
-EP44-RM1 |
Non-return valve |
|||
-EP45 |
Cooling system 1 |
|||
-EP45-AA25 |
AXC module, cooling system 1 |
Included in AXC 50 |
067 060 |
|
-EP45-GP10 |
Circulation pump, cooling system 1 |
Modbus: 44754 |
||
-EP45-QN12 |
Reversing valve, cooling |
Modbus: 44751 See the valve’s manual for a port description. |
||
-EP25 |
Passive cooling system |
AXC 50 |
067 296 |
|
-EP25-AA25 |
AXC module, cooling |
Included in AXC 50 |
||
-EP25-BT64 |
Temperature sensor, cooling flow line |
Included in AXC 50 Modbus: 40045 |
||
-EP25-BT65 |
Temperature sensor, cooling return line |
Included in AXC 50 Modbus: 40046 |
||
-EP25-EP13 |
Supply air coil/fan coil |
|||
-EP25-GP13 |
Circulation pump, cooling |
Modbus: 44754 |
||
-EP25-QN18 |
Mixing valve, cooling |
Modbus: 44278 See the valve’s manual for a port description. |
||
-EP25-RM1 |
Non-return valve |
|||
-EQ1 |
Active cooling. |
NIBE ACS 45 |
067 195 |
|
-EQ1-AA25 |
AXC module, cooling |
Included in NIBE ACS 45 |
||
-EQ1-BT57 |
Temperature sensor, collector |
Included in NIBE ACS 45 Modbus: 40155 |
||
-EQ1-BT64 |
Flow temperature sensor, cooling |
Included in NIBE ACS 45 Modbus: 40045 |
||
-EQ1-BT75 |
Temperature sensor, flow line after heat dump |
Included in NIBE ACS 45 Modbus: 40156 |
||
-EQ1-EP6 |
Heat exchanger |
|||
-EQ1-GP10 |
Circulation pump |
Modbus: 44322 |
||
-EQ1-GP12 |
Circulation pump |
Included in NIBE ACS 45 Modbus: 44322 |
||
-EQ1-GP14 |
Circulation pump for heat dump |
|||
-EQ1-GP20 |
Circulation pump, heat dump |
Modbus: 44752 |
||
-EQ1-QM40.1 |
Shut-off valve |
|||
-EQ1-QM40.2 |
Shut-off valve |
|||
-EQ1-QN12 |
Reversing valve, cooling |
Modbus: 44751 See the valve’s manual for a port description. |
||
-EQ1-QN18 |
Shunt valve, cooling shunt |
Modbus: 44278 See the valve’s manual for a port description. |
||
-EQ1-QN36 |
Shunt valve, heating shunt |
Modbus: 44277 See the valve’s manual for a port description. |
||
-EQ1-RM1 |
Non-return valve, heat dump |
|||
-EQ1-QN12 |
Reversing valve, cooling |
Modbus: 44751 See the valve’s manual for a port description. |
||
-EQ2 |
Heat dump |
|||
-EQ2-EP6 |
Heat exchanger |
|||
-EQ2-GP14 |
Circulation pump for heat dump |
|||
-EQ2-GP10 |
Circulation pump, heat dump |
Modbus: 44752 |
||
-EQ2-QN36 |
Mixing valve, heat dump |
Modbus: 44277 See the valve’s manual for a port description. |
||
-QZ1 |
Hot water circulation (HWC) |
|||
-QZ1-AA25 |
AXC module |
Included in AXC 50 |
067 193 |
|
-QZ1-BT70 |
Supply temperature sensor, HWC |
Included in AXC 50 Modbus: 40147 |
||
-QZ1-BT82 |
Return line sensor, HWC |
Included in AXC 50 Modbus: xxxxxx |
||
-QZ1-FQ3 |
Mixer valve, HWC |
|||
-QZ1-GP11 |
Circulation pump, HWC |
Modbus: 43180 |
||
-QZ1-QN2 |
4-way valve, HWC |
See the valve’s manual for a port description. |
||
-QZ1-RM1 |
Non-return valve, HWC |
|||
-QZ1-RN1 |
Trim valve, HWC |
|||
-QZ1-RN4 |
Trim valve, HWC |
|||
-XL27 |
Filling connection |
|||
-QM34 |
Shut off valve, brine out |
|||
-XL27 |
Filling brine |
|||
-XL28 |
Filling brine |
|||
-FL2 |
Miscellaneous |
|||
-BP5 |
Pressure gauge, heating medium |
|||
-BP6 |
Pressure gauge, brine |
|||
-CM1 |
Expansion vessel, heating medium |
|||
-CM2 |
Level vessel, brine |
Included in F1345/F1355 |
Level vessel in open system |
|
-CM3 |
Expansion vessel, brine |
|||
-CM4 |
Expansion vessel, hot water |
Included in F1345/F1355 |
||
-CP10 |
Buffer vessel |
UKV 100/ UKV 200/ UKV 300/ UKV 500 |
Size varies depending on heat pump and system volume |
|
-CP10.1 |
Buffer vessel |
UKV 100/ UKV 200/ UKV 300/ UKV 500 |
Size varies depending on heat pump and system volume |
|
-CP10.2 |
Volume vessel, cooling |
UKV 200/UKV 300 |
080 321 / 080 330 |
Condensation-insulated vessels for cooling |
-CP10.3 |
Buffer vessel |
UKV 100/UKV 200/UKV 300/UKV 500 |
Size varies depending on heat pump and system volume |
|
-FL1 |
Safety valve, hot water |
|||
-FL2 |
Safety valve, heating medium |
|||
-FL3 |
Safety valve, brine |
Included in F1345/F1355 |
||
-FL311xx |
Safety valve, brine |
Included in F1355/F1345-24/30/F1345/F1355 |
||
-FQ1 |
Mixing valve |
Thermal |
||
-HQ1 |
Particle filter, brine |
Included in F1345-24/30 |
||
-HQ2 |
Particle filter, brine |
Included in F1345-24/30 |
||
-HQ3 |
Particle filter, heating medium |
Included in F1345-24/30 |
||
-HQ4 |
Particle filter, heating medium |
Included in F1345-24/30 |
||
-RM1 |
Non-return valve |
|||
-RM1.1 |
Non-return valve |
|||
-RM1.2 |
Non-return valve |
|||
-RM1.3 |
Non-return valve |
|||
-RM2 |
Non-return valve |
|||
-RM3 |
Non-return valve |
|||
-RN1.1 |
Trim valve |
|||
-RN1.2 |
Trim valve |
|||
-RN1.3 |
Trim valve |
|||
-RN2.1 |
Trim valve |
|||
-RN2.2 |
Trim valve |
|||
-RN3.1 |
Trim valve |
|||
-RN3.2 |
Trim valve |
|||
-RN4.1 |
Trim valve |
|||
-RN4.2 |
Trim valve |
|||
-RN5.1 |
Trim valve |
|||
-RN5.2 |
Trim valve |
|||
-QM1 |
Drain valve, heating medium |
|||
-QM30 |
Shut-off valve, hot water |
|||
-QN17 |
Pressure reduction valve |
|||
-WM3 |
Tundish, cold water |
Included in F1345/F1355 |
||
-WM4 |
Tundish, T&P valve |
Included in F1345/F1355 |
Designations according to standard EN 81346-2.